Terminated Products
Solid State Motor Protection Relay (RC820)

The 2E relay, RC820 is a three phase overload relay, which also provides single-phase protection. Ground fault and phase reversal modules are available.

Solid State Motor Protection Relay (RC820)

Feature

  • UL listed and CSA certified, safety for any application
  • Both surface and flush mounts are available

Specification

Specification List

This table can be scrolled horizontally.

Specification List
TYPE FORM RC820-HP1Y RC820-HP2Y RC820-HP3Y
Applicable circuit Three phase, 50/60Hz, 600VAC
Protection functions Overload and single phase function
Rated current Rated ampere-turns 7AT 55AT 110AT
Setting range 75 to 150% of rated AT
Over load
operating
characteristics
Ultimate trip current 105 to 125% of setting current
Operating
setting range
3 to 40 seconds for cold starting characteristics
at 600% of setting current
Single phase
operating
characteristics
Minimum
operating current
85% of setting current
flowing in the conducting phase
Operating time 4 seconds or less
Rated control voltage 100-120VAC/200-240VAC phase 50/60Hz
Power
consumption
Control power circuit 2VA
Detecting circuit 0.3VA / phase at rated current
Application
conditions
Ambient temperature -10 - 60oC
Relative humidity 45 -85% (No condensation)
Output contact Contact arrangement 1NO/NC (Form C)
Contact capacity Resistive 125VAC-3A
250VAC-1.5A
L/R=7ms 30VDC-3A
48VDC-2A